
- Research Notes -
|
Backflow Prevention and Safety Devices for Chemigation
by Kenneth H. Solomon and David F. Zoldoske
CATI Publication #981201 © Copyright August 1998, all rights reserved
ABSTRACT
This paper discusses potential hazards to the water source when "chemigating"
under various conditions of irrigation system and circumstance. Current U.S. Environmental
Protection Agency requirements are presented for backflow prevention and safety devices to
protect the water source when chemigating. A discussion of alternate permissible devices
to achieve specific purposes is included. The differences in requirements for protection
of urban, potable water supplies and typical agricultural water supplies are noted, and
specifications for an agricultural "chemigation valve" incorporating necessary
safety functions are given. Field experience with failure rates of double check valve
assemblies is reviewed. Other aspects of the necessary safety considerations, such as
system interlocks and flow checks, are also discussed.
INTRODUCTION
"Chemigation" is a general term used to describe the addition of a variety of
agricultural chemicals to an irrigation system, usually for the purpose of distributing
the chemicals throughout the irrigated area along with the irrigation water. Other, more
specific terms are used to describe the application of given materials through an
irrigation system, with the prefix to "-gation" indicating the type of material
applied: fertigation (fertilizers); fungigation (fungicides); insectigation
(insecticides); and herbigation (herbicides) (Smith, 1990). Chemigation may also include
the introduction of chlorine, acids or other chemicals for the purpose of water treatment
or cleaning of the irrigation system components. Benefits of chemigation include
economical application, the potential for frequent, precise applications to match seasonal
crop needs, and a reduction in soil compaction and mechanical damage to the crop (due to
reduced tractor and sprayer operations in the field) (Zoldoske and Jorgensen, 1990).
From the standpoint of backflow prevention and safety, the type of material injected
into the irrigation system may be significant. Different levels of toxicity and
concentration lead to different safety risks. For example, some government agencies
(local, state or national) allow fertigation, but prohibit other forms of chemigation on
the grounds that the chemicals (other than fertilizers) used are either inherently toxic
(biocides: fungicides, herbicides, insecticides, nematicides, etc.) or dangerous (acids).
Other agencies allow all forms of chemigation, but allow a lower level of backflow
prevention and safety assurance when only fertigation is to be done.
The Center for Irrigation Technology position is that all systems employing any form of
chemigation should incorporate backflow prevention and safety devices commensurate with
the injection of the most hazardous class of chemicals, i.e., biocides. The rationale is
that since the equipment for injection of fertilizers is the same as for the injection of
biocides, fertigation systems are potentially chemigation systems. Government agencies
cannot assess the intent of the applicator from the equipment configuration alone. Unless
an inspector is present during each irrigation event, there is no way to enforce a ban on
the injection of biocides. Therefore all injection systems should be treated as biocide
injection systems, and protected accordingly.
WATER SOURCE CONTAMINATION HAZARDS WITH CHEMIGATION
In the absence of properly installed and functioning backflow prevention and safety
devices, contamination of the water supply can occur in the event of certain failures in
the irrigation or injection system. Potentially hazardous circumstances include the
following (ASAE, 1994):
(1) Any shutdown of the irrigation pumping plant. If the main irrigation pump shuts
down, the direction of main water flow could reverse. This reverse flow could be driven by
water from an elevated system exerting a backpressure on the pump or injection point, or
by water draining towards a lower level source (water falling back down a well), creating
back-siphoning which could draw chemicals into the water source.
(2) Operation of the injection equipment after an irrigation pumping plant shutdown. If
the main irrigation line is not pressurized, the injection pump could force concentrated
chemicals or a mixture of water and chemicals to flow into the water source.
(3) A failure of the injection equipment while the irrigation pump is still operating.
Pressurized water from the irrigation line could flow back through the chemical holding
tank, possibly causing its overflow and spillage of chemicals. The chemical spill could
pose a hazard in itself, or could drain towards and enter the water source.
AGRICULTURAL VERSUS POTABLE WATER SUPPLY PROTECTION
Backflow prevention equipment for protecting potable water supplies has been available for
many decades (Anon., 1993). However, these devices are generally far too expensive for
widespread implementation in agricultural installations. Fortunately, some of the
requirements for potable supply protection devices are more strict than may be necessary
in an agricultural setting. It is this fact that allows agricultural
"chemigation" valves to be manufactured and commercially available at reasonable
prices. For example (Zoldoske, 1995), an agricultural chemigation valve of 100 mm (4 inch)
nominal size may be purchased for approximately one-fourth the cost of a reduced pressure
principle device (RP) of the size suitable for potable water supply protection (ag
chemigation valve ~$435; RP device for potable water ~$1,645). The difference is even more
pronounced at the larger sizes. For example, an agricultural chemi-gation valve of 250 mm
(10 inch) nominal size may be purchased for approximately one-seventh the cost of a
reduced pressure principle device (RP) of the same size suitable for potable water supply
protection (ag chemi-gation valve ~$840; RP device for potable water ~$5,980.
Some of the key points of difference are serviceability, pressure rating, operating
time and potential risk. It is required (Anon., 1993) that potable water supply devices
can be repaired without removal from the line. This isn't necessary within an agricultural
setting. Devices for potable water supply are usually rated at 12
Bars (175 PSI). Agricultural chemigation valves may use a lower
rating. Most potable water devices operate, or at least are under pressure, nearly
continuously and endure far more hours of operation per year and per life cycle than
agricultural chemigation.
Finally, the agricultural condition is inherently far less risky than the potable water
supply condition. If chemicals are introduced into a potable water supply, potentially
they may be ingested directly by humans. Contamination of an agricultural water source,
such as a well, is less problematic. The contamination will be further
diluted in the
ground water, or as it is re-pumped from the well, and it should not be directly consumed
by humans.
BACKFLOW PREVENTION AND SAFETY REQUIREMENTS
An air gap separation is generally regarded as the highest form of protection against
backflow contamination (Anon., 1993; Zoldoske and Jorgensen, 1990). An air gap is a
physical separation between the discharge end of water supply pipe and an open
receiving vessel, for example a reservoir or standpipe. The separation must be at least
twice the diameter of the supply pipe, but in no case less than 25 mm (1 inch). An air gap
separation is regarded as sufficient protection for even potable water supplies against
chemigation backflow hazards. Air gap protection is often well suited for surface
irrigation systems. A disadvantage of air gap protection is that the receiving vessel in
not pressurized, and so the water may need to be re-pumped to overcome elevation
differentials or to achieve the operating pressure required by a pressurized irrigation
system.
In the absence of a suitable air gap separation, water source protection from
chemigation systems may be achieved with specific combinations of equipment and system
interlocks. U.S. Environmental Protection Agency (EPA) regulations specify backflow
prevention and related equipment to be used when chemigating. The following descriptions
of equipment and assemblies are based on current EPA regulations as cited by Smith (1990)
and on the relevant standard, EP 409.1, from the American Society of Agricultural
Engineers (ASAE, 1994).
1. Suggested Irrigation Pipeline Equipment
1a. A check valve must be installed between the water source and injection point, to
prevent water in the irrigation pipeline from moving back towards the water source.
1b. A low pressure drain must be installed upstream of the check valve, usually
directly below the vacuum relief valve (1c), to dispose of small volumes of fluid which
may leak past the check valve.
1ab'. An alternate which substitutes for check valve (1a) and low pressure drain (1b)
is a gooseneck pipe loop in the main water line between the irrigation water pump and
injection point. The gooseneck pipe loop must contain a vacuum relief (or combination air
and vacuum relief) valve at the apex of the loop. The bottom of the pipe at the loop apex
must be at least 0.6 m (24 in) above the highest water emitting device in the system. The
chemical injection port must be downstream of the apex of the pipe loop and at least 0.15
m (6 in) below the bottom of the pipe at the loop apex.
1c. A vacuum relief valve must be installed upstream of the check valve, usually
directly above the low pressure drain (1b), or at the apex of the gooseneck pipe loop, to
prevent formation of a vacuum which could cause backsiphonage.
1c'. An alternate which substitutes for the vacuum relief valve (1c) is a combination
air and vacuum relief valve.
1d. A low pressure sensor (or flow sensor) must be installed downstream of the
irrigation pump to identify pressures too low for proper chemical application or low
pressure conditions signifying irrigation pump stoppage or failure.
2. Suggested Injection Line Equipment (when using a metering type
injection pump, such as a positive displacement or diaphragm pump, between chemical
holding tank and injection point)
2a. An anti-backflow injection valve (a spring loaded check valve with an opening
pressure of at least 70 kPa [10 PSI]) must be installed at the point where the injection
line joins the main irrigation line to prevent water from flowing back into the chemical
holding tank should the injection pump fail, and to prevent gravity drainage from the
chemical holding tank when the irrigation line is not pressurized.
2b. A normally closed solenoid or hydraulically operated valve must be installed
between the chemical holding tank and the injection pump to prevent unwanted flow into or
out of the chemical holding tank.
2b'. An alternate which substitutes for the normally closed valve (2b) is a check valve
to prevent water from flowing back towards the chemical holding tank. The check valve
shall be spring loaded with an opening pressure of at least 70 kPa (10 PSI) to prevent
gravity drainage from the chemical holding tank.
2b''. Another alternate which substitutes for the normally closed valve (2b) is a
vacuum relief valve between the injection pump and the anti-backflow injection valve (2a).
The vacuum relief valve must be positioned at least 0.3 m (12 in) above the highest fluid
level possible inside the chemical holding tank, and must be the highest point
in the injection line. The valve must open at 0.15 m (6 in) water vacuum
or less. The vacuum relief valve may be a combination air and vacuum relief valve.
3. Suggested Injection Line Equipment When Using A Venturi Injector
(Note: The venturi injector may be inserted directly into the main irrigation line, into a
bypass line, or into a bypass line boosted with an auxiliary water pump.)
3a. A check valve must be installed in the line from the chemical holding tank to the
venturi to pre-vent flow back towards the chemical holding tank.
3b. A normally closed solenoid or hydraulically operated valve must be installed
between the chemical holding tank and the injection point to prevent unwanted flow into or
out of the chemical holding tank.
3ab'. In bypass systems, as an alternate to placing both valves (3a and 3b) in the
injection line, the check valve (3a) may be installed in the bypass line upstream of the
venturi, and the normally closed valve (3b) may be installed in the bypass line downstream
of the venturi.
4. Suggested Power and System Interlocks
4a. Interlock the injection pump or venturi bypass booster pump with main irrigation
pump so that the injection or booster pump automatically shuts off when the main
irrigation pump stops.
4b. Interlock the normally closed solenoid or hydraulically operated valve (2b or 3b)
with the injection pump or venturi bypass booster pump so that the valve closes upon shut
down of the injection pump or venturi bypass booster pump or system.
4c. Interlock the normally closed solenoid or hydrau-lically operated valve (2b or 3b)
with the low pressure or flow sensor (1d) so that the valve opens only when the main
irrigation line is adequately pressurized.
SPECIFICATIONS FOR AGRICULTURAL CHEMIGATION VALVES
Agricultural "chemigation" valves are commercially available that combine the
recommended main line check valve, low pressure drain and air/vacuum relief valve in one
product. Specifications for these valves are as follows.
CIT suggests that the chemigation valve's check shall be spring loaded so that a
pressure greater than 2 kPa (6 inches of head, 1/4 PSI) is required to open the
valve. The check must be able to withstand for one minute an internal hydrostatic pressure
of twice the rated pressure of the valve. It shall withstand for 16 hours, without leakage
at the valve seat, an internal hydrostatic pressure equivalent to the head of a 1.5 m (5
ft) column of water retained within the downstream portion of the valve body. No leakage
past the clappers is acceptable in either case.
The combination air relief and vacuum relief valve shall have a nominal size at least
25 percent the nominal size of the chemigation valve. The vacuum relief valve must be open
at pressures below 10 kPa (1.5 PSI).
The automatic low pressure drain valve shall be a minimum 20 mm (3/4 inch) nominal size
attaching to the chemigation valve at the lowest point of the upstream side of the check
valve. It shall be pressure activated with an opening point of 10 ± 3 kPa (1.5 ± 0.5
PSI). The drain valve must close above 7 kPa (2 PSI), and must be able to be closed
externally to facilitate testing.
The chemigation valve will have an inspection port of at least 100 mm (4 inch) diameter
on the top side of the valve, directly above the low pressure drain. This inspection
port may be combined with the mounting of the combination air/vacuum relief valve.
The chemigation valve shall have test ports on each side of the check valve, at the
elevation of the centerline of the chemigation valve. The chemigation valve shall be rated
at 8.5 Bars (125 PSI) or higher.
The chemigation valve shall be marked with the following: name or identifying symbol;
nominal size; model number or catalog designation; rated pressure; mark indicating date of
manufacture; arrow showing direction of flow; intended orientation (horizontal or
vertical) if this affects the operation of the valve; and a unique serial number for
identification purposes.
DOUBLE CHECK VALVE FAILURE RATES
Data reported to the Pacific Northwest Section of the American Water Works Association
(Bratton, 1992) over the three-year period 1979-1980-1981 is summarized in Table 1. The data were collected within the jurisdictions of the
Portland Water Bureau of Oregon; the Seattle Water Department, Tacoma Water Department,
and Modern Electric & Water Company of Washington; and the Richmond Water Department
and Vancouver Water Department of British Columbia. Each device is required to be tested
at least annually (Anon., 1993), so the failure rates listed may be considered annual
rates.
Table 1 implies that while there is some risk reduction due
to the redundancy offered by the second check valve, it is not the one or two order of
magnitude reduction that might be expected if failure of the two check valves were in fact
independent. Conditions that tend to foul the first check valve will also tend to foul the
second: one-third of the occasions when the first check failed, the second one did also.
The devices referred to in Table 1 are designed for backflow
protection in potable water supply systems. Typically, their operating conditions differ
from agricultural installations in that (1) they are dealing with relatively clean water,
and (2) they are operating, or at least are under pressure, nearly continuously. It is not
known how failure rates of devices under agricultural conditions would compare with the
rates in Table 1; however, we believe they would be somewhat
higher due to the higher incidence of sediments or contaminants in agricultural waters.
This suggests that failure rates of single check valves in agricultural backflow
prevention devices might be on the order of three percent to five percent per
service-year. This further suggests that in order to protect agricultural water supplies,
backflow prevention devices should be checked at the beginning of each irrigation
(chemigation) season, and perhaps once or twice at other times during the season.
ADDITIONAL SAFETY CONSIDERATIONS
An independent water source should be available near the chemical injection site for
washing off any chemicals that contact the skin. Note that a hose and/or outlet from the
main water supply or irrigation pipeline is not appropriate for this purpose, unless it is
also protected from backflow with a suitable device. A hose connected to an outlet
downstream of the chemical injection point may discharge chemicals or a mixture of water
and chemicals rather than the fresh water needed for washing. A hose connected between the
backflow prevention device and the water source will dispense fresh water, but itself
constitutes a contamination hazard if not protected from backflow. Consider, for example,
what would happen if the hose, used to wash out or dilute chemicals in the chemical
holding tank, were left in the tank during a backsiphonage situation. Chemicals to be
injected would be drawn back through the hose directly into the water source. One
acceptable alternative is to have a separate tank and spigot for fresh water only, not
connected to the chemigation system in any way. Another would be to install a small
backflow prevention device upstream of the hose connection point.
Workers should use proper goggles and protective clothing when mixing chemicals.
Operating instructions and safety precautions for the injection system should be posted
where they can easily be seen by workers. Pressurized chemical holding tanks should carry
warnings against inadvertent opening when pressurized.
The site should be graded so that any chemical spill runs away from the water source.
Chemical storage tanks should be provided with secondary containment, such as an earthen
basin, lined with impermeable material, with a capacity at least 125 percent of the
chemical storage tanks.
Filters for microirrigation should not be backflushed during chemical injection.
Special arrangements may be necessary for filtration systems with automatic backflush
cycles.
SUMMARY
With proper selection, installation and maintenance of chemigation equipment, including
backflow prevention and safety devices, applying chemicals through an irrigation system
can be an effective, economical and safe practice. Commercially available
"chemigation" valves, combined with appropriate system interlocks, provide
sufficient backflow protection for agricultural water supplies.
Many states and/or counties lack backflow prevention standards on agricultural water
supplies. Others maintain strict requirements related to potable water supplies. The
purpose of this paper has been to explore safe backflow prevention alternatives between
these two potentially extreme positions.
REFERENCES
Anonymous. 1993. Manual of Cross-Connection Control, 9th Edition. Foundation for
Cross-Connection Control and Hydraulic Research, University of Southern California, Los
Angeles, California, 307 pages.
ASAE. 1994. ASAE Engineering Practice EP 409.1 (Dec. 93): Safety Devices for
Chemigation. American Soc. of Agricultural Engineers, St. Joseph, MI, 3 pages.
Bratton G.N. 1992. Personal Communication. Schaefer & Bratton Engineers,
Coupeville, Washington, USA.
Smith E.M. (editor). 1990. Chemigation Workbook. Texas Agricultural Extension Service
Bulletin B-1652, College Station, Texas, 61 pages.
Zoldoske D.F. 1995. Conversations With Industry Sources. Center for Irrigation
Technology, California State University, Fresno, California.
Zoldoske D.F., and Jorgensen G.S. 1990. Careful Chemigation Could Help Growers. Western
Fruit Grower, April 1990, 110(4):26,28.
-
{ CATI ,
CIT , CIT - Research
Publications }
-
Copyright © 2000. All rights reserved.
CALIFORNIA AGRICULTURAL TECHNOLOGY INSTITUTE - CATI
College of Agricultural Sciences and
Technology
California State University, Fresno